USE THESE CHARTS TO DETERMINE TRANSFORMER SIZE REQUIRED
SINGLE PHASE
TRANSFORMER FULL LOAD CURRENT IN AMPS |
|
KVA |
RATED LINE VOLTAGE |
120 |
240 |
480 |
600 |
|
1 |
8.3 |
4.2 |
2.1 |
1.6 |
2 |
16.7 |
8.4 |
4.2 |
3.2 |
3 |
25.0 |
12.5 |
6.3 |
5.0 |
5 |
41.7 |
20.8 |
10.4 |
8.3 |
7.5 |
62.5 |
31.2 |
15.6 |
12.5 |
10 |
83.4 |
41.6 |
20.8 |
16.7 |
15 |
125 |
62.5 |
31.2 |
25.0 |
25 |
208 |
104 |
52.1 |
41.6 |
37.5 |
312 |
156 |
78.2 |
62.5 |
50 |
416 |
208 |
104 |
83.3 |
75 |
625 |
312 |
156 |
125 |
100 |
833 |
416 |
208 |
167 |
150 |
1250 |
625 |
312 |
250 |
167 |
1391 |
696 |
348 |
278 |
250 |
2083 |
1041 |
521 |
417 |
333 |
2775 |
1387 |
684 |
555 |
500 |
4166 |
2083 |
1042 |
833 |
|
|
SINGLE PHASE CALCULATION
kVA = Volts x Amps
1000
Amps = kVA x 1000
Volts |
|
THREE PHASE
TRANSFORMER LOAD CURRENT PER LINE IN AMPS |
|
KVA |
RATED LINE VOLTAGE |
208 |
240 |
480 |
600 |
|
6 |
16.6 |
14.4 |
7.2 |
5.8 |
9 |
25.0 |
21.6 |
10.8 |
8.7 |
10 |
28.0 |
24.0 |
12.0 |
9.6 |
15 |
41.6 |
36.1 |
18.1 |
14.4 |
30 |
83.3 |
72.3 |
36.1 |
28.9 |
45 |
125 |
108 |
54.0 |
43.2 |
75 |
208 |
181 |
90.5 |
72.1 |
112.5 |
312 |
272 |
136 |
108 |
150 |
416 |
360 |
180 |
144 |
225 |
624 |
541 |
270 |
216 |
300 |
832 |
722 |
361 |
288 |
450 |
1250 |
1080 |
542 |
433 |
500 |
1388 |
1203 |
601 |
481 |
600 |
1666 |
1445 |
722 |
578 |
|
|
THREE PHASE CALCULATION
kVA = 1.73 x Volts x Amps
1000
Amps = kVA x 1000
1.73 x Volts |
|
kVA |
SOUND LEVEL (AVERAGE) |
0-9 |
40 db |
10-50 |
45 |
51-150 |
50 |
151-300 |
55 |
301-500 |
60 |
501-600 |
62 |
|